A frozen pipe rarely bursts where the ice is. Research by the Building Research Council at the University of Illinois found that once ice fully blocks a pipe, the pressure builds downstream, in the water trapped between the blockage and a closed faucet or valve. The pipe usually fails there, where little or no ice has formed.
That detail explains most of what goes wrong with frozen pipes in commercial buildings. The cold spot sits in a roof plenum, a loading dock wall or an unheated stairwell, but the water comes out somewhere else, often on a floor nobody is watching, and often when the thaw starts rather than during the freeze itself.
This guide covers why pipes freeze and burst, which systems in a commercial building are exposed first, how facility teams prevent frozen pipes, and how flow monitoring catches the burst that prevention missed.
Why Frozen Pipes Burst, and Why It Often Happens After the Freeze
Water expands as it freezes. In a pipe that is open at one end, that expansion has somewhere to go. Once ice forms a complete plug, the section between the plug and the next closed outlet becomes a sealed chamber. Every bit of additional ice raises the pressure in that chamber until the weakest point gives way: a joint, a fitting, a bend or a thin stretch of pipe.
The same research set a practical “temperature alert threshold” of 20°F: field tests found that uninsulated pipes in an unconditioned space began to freeze when the outside temperature fell to 20°F or below. Wind and drafts lower that threshold further, because moving air pulls heat from a pipe much faster than still air.
The damage often shows up later. While the line is frozen, the ice holds the crack closed. When temperatures rise and the ice melts, the system pressurizes again and water flows out of a split that formed days earlier. In a commercial building, that moment is frequently a weekend or an overnight period with nobody on site.
What a Frozen Pipe Costs a Commercial Building
Freeze losses are expensive even before business interruption is counted. When Philadelphia Insurance Companies studied 433 burst pipe claims, its average loss related to frozen pipes was $27,000, and its most expensive single claim was $1.7 million. The claims were split almost evenly between sprinkler systems and domestic water pipes.
On the property side of the market as a whole, State Farm reported more than 20,000 freeze-related water claims from 2024 through June 2025, with over $628 million in paid losses and an average payment above $30,000.
A commercial building adds costs that a claim figure leaves out: tenant spaces taken out of use, damaged equipment and inventory, lease disputes, and the deductible and premium consequences of a large water claim. The size of the bill depends less on the crack itself than on how long water runs before someone closes a valve.
Where Commercial Buildings Freeze First
Freeze risk in a commercial building is concentrated in a predictable set of places. These are the systems facility teams map first:
- Rooftop and exterior equipment. Roof tanks, makeup lines and piping that runs across the roof or through penthouse plant rooms are exposed to the full wind chill.
- Perimeter walls and entrances. Pantry and restroom supply lines in exterior walls, loading docks, vestibules and stairwells sit close to outside air and often lose heat through gaps in the envelope.
- Unconditioned voids. Ceiling plenums, parking garages and crawl spaces carry pipe runs through spaces that are rarely heated to occupied temperatures.
- Seasonal systems. Irrigation lines and exterior hose connections freeze when they are not drained and isolated before winter.
- HVAC water. Coils exposed to outdoor air and the pipework of HVAC loops are vulnerable when a damper sticks open or a pump stops.
- Vacant or setback spaces. Empty floors, spaces between tenants and buildings on holiday setback run colder than the rest of the building, and nobody notices a problem there for days.
How to Prevent Frozen Pipes in a Commercial Building
The household advice is familiar: insulate exposed pipes, keep the heat on and let a faucet drip. Each of those has a commercial-scale version, and each works best as part of a seasonal program rather than a reaction to a forecast.
Before the season
- A freeze-risk survey. The survey identifies every pipe run in an exterior wall, unheated void or rooftop location, and records which water system and shutoff valve serves it.
- Insulation and heat trace. Pipe insulation slows heat loss; heat trace cable, with working thermostats and power, keeps vulnerable runs above freezing. Both are checked before the first cold spell, not during it.
- A sealed envelope. Gaps around penetrations, damaged dock seals and doors that do not close fully let in the drafts that push the freeze threshold above 20°F.
- Drained seasonal lines. Irrigation systems and exterior connections are isolated, drained and left open at the outlet so that no trapped water remains.
- Controls that cover empty spaces. Building management system setpoints and low-temperature alarms cover vacant floors and after-hours schedules, and heating equipment has a plan for a power cut.
During a cold snap
- Minimum temperatures in unoccupied areas. Setback schedules in vacant spaces are suspended while temperatures stay low.
- Pressure relief on the most exposed runs. A slightly open outlet relieves the pressure that builds behind an ice plug. The Illinois research is clear that this works by preventing pressure buildup, not by stopping the water from freezing.
- Warm air to perimeter cabinets. Open cabinet doors in exterior-wall pantries and restrooms let building heat reach the pipes inside.
After the freeze
The thaw is the riskiest period, because it is when a split pipe starts to leak. Frozen sections are thawed slowly and from the open outlet back toward the frozen spot. Valves are reopened gradually, since fast reopening sends pressure surges through lines that may already be damaged (see our glossary entry on water hammer). Repaired sections are tested before they return to service, and our guide to hydrostatic testing explains how.
Catching a Burst in Minutes, Not on Monday
Prevention reduces the number of frozen pipes. It does not reduce the damage from the one that bursts anyway. That depends on detection and response, and in a commercial building the response has to work at 3 a.m. on a Sunday.
A burst looks unmistakable in flow data. A flow meter on the affected water system records a sudden jump to a rate far above anything that system normally carries, at a time when nobody is using it. Our platform compares that flow against the system’s learned pattern and raises a high flow alert within minutes.

Where automatic shutoff is enabled, the valve on that water system closes without waiting for someone to drive in. The rest of the building keeps its water, because the shutoff is local to the system that failed. Shutoff behavior is set per water system, so a roof tank line can close automatically while a domestic riser stays on alert-only, according to each building’s own policies.
Watching Every Building Through a Cold Snap
A regional freeze does not hit one building. It hits a portfolio at once, and the teams responsible need one view of where water is flowing that should not be.
Flow data also shows the damage a freeze leaves behind. A split fitting that was not caught on the day it thawed can keep leaking at a low rate for weeks. That kind of steady background flow is invisible on a utility bill until the next reading, but it stands out against a system’s normal pattern. Our guide to commercial water leak detection systems covers how that detection works across a building.
Freeze events are becoming less predictable, including in regions that rarely planned for them. Our article on climate volatility and freeze events looks at that trend and what it means for building owners.
Frequently Asked Questions
At what temperature do pipes freeze?
Water freezes at 32°F, but pipes inside a building are partly protected by the structure around them. University of Illinois field tests found that uninsulated pipes in an unconditioned space began to freeze when the outside temperature fell to 20°F or below. Drafts, wind and gaps in the building envelope can cause freezing at higher outside temperatures.
Does a frozen pipe always burst?
No. A pipe bursts when pressure builds between an ice blockage and a closed outlet. If that pressure has somewhere to go, for example through a slightly open faucet, the pipe can freeze without failing. Pipes with existing weak points, such as old joints or corroded sections, are more likely to fail.
Why do pipes leak after the thaw instead of during the freeze?
While a pipe is frozen, the ice holds a crack closed and no water flows. When the ice melts, the system pressurizes again and water escapes through the damage. That is why the thaw, often a weekend or an overnight period, is when most freeze-related water damage starts.
How quickly can a burst pipe be stopped?
That depends on detection and shutoff. Without monitoring, a burst is found when someone sees the water, which can be days later in an empty space. With flow monitoring, a burst is flagged within minutes, and with automatic shutoff the valve on the affected system closes without anyone needing to be on site.